Grid-Enhancing Technologies: Getting More From the Wires We Already Have

Before building new transmission, utilities can often squeeze more capacity out of existing lines. Here is how dynamic line ratings, power flow controls and reconductoring work.

Published

on

Parallel power lines

New transmission lines can take a decade or more to build. Meanwhile, demand from data centers and electrification is growing now. That mismatch has drawn attention to grid-enhancing technologies, often called GETs, which aim to increase the capacity or flexibility of existing transmission infrastructure without building entirely new lines.

Dynamic line ratings

Every transmission line has a rating, the maximum amount of power it can safely carry. The limit is often set by heat: as current flows, the line warms and sags. If it sags too far, it can come too close to trees or the ground.

Traditionally, many lines use static ratings based on conservative assumptions, such as a hot day with little wind. In reality, conditions are often cooler and windier, allowing the line to carry more power safely. Dynamic line ratings use sensors and weather data to calculate a line’s actual capacity in real time. On many days, this can reveal additional capacity that would otherwise go unused.

Advertisement

Ambient-adjusted ratings are a simpler step, adjusting ratings based on air temperature, and federal rules have moved to require them more broadly.

Power flow control and smarter switching

Power on a meshed grid follows the path of least resistance, not necessarily the path operators would prefer. That can overload one line while a parallel line sits underused. Advanced power flow control devices let operators push power away from congested lines and toward lines with spare capacity, improving how the network is used overall.

Operators can sometimes relieve congestion simply by changing how the network is configured, opening or closing certain breakers to reroute flows. Topology optimization software analyzes the grid and identifies switching actions that reduce congestion while keeping the system reliable.

Reconductoring

Reconductoring is not always classified as a GET, but it is closely related. It involves replacing existing wires with advanced conductors that can carry more current, often with less sag, using the same towers and rights-of-way. Because it avoids new routes, reconductoring can sidestep many siting and permitting obstacles that slow new lines.

The main options include:

Advertisement
  • Dynamic line ratings and ambient-adjusted ratings.
  • Advanced power flow controllers.
  • Topology optimization software.
  • Advanced conductors used in reconductoring projects.

Limits and adoption

GETs are not a complete substitute for new transmission. They can relieve specific constraints and buy time, but large increases in demand or new generation in distant areas eventually require new lines. Adoption has also been slower than some advocates hoped, partly because utility incentives have historically favored capital investment in new infrastructure over operational improvements.

Why it matters for data centers

For a data center waiting on grid capacity, the difference between needing a new line and needing a sensor upgrade can be years. GETs can sometimes unlock capacity for new loads or generation sooner, while longer-term transmission expansion proceeds. Regulators and grid operators are increasingly asking utilities to consider these technologies in their planning, making them an important part of the toolkit for a fast-growing grid.

How a Dynamic Line Rating Works in Practice

It can help to picture what actually happens when a utility moves from a static rating to a dynamic one on a single line.

  1. Measure conditions. Sensors are installed along the line, or the utility uses detailed weather data, to track air temperature, wind speed and direction, sunlight, and sometimes the line’s own temperature or sag.
  2. Model the conductor. Software uses those inputs to estimate how hot the wire will get at different levels of current. Wind blowing across a line cools it; sunshine and hot air warm it.
  3. Calculate the rating. The system computes how much current the line can carry while staying within safe temperature and clearance limits, often for the current hour and the next several hours.
  4. Feed the operator. Those ratings flow into the control room and, in organized markets, into the market software that decides which generators run.
  5. Keep a margin. Operators still build in safety buffers, and if sensors fail or data looks unreliable, they fall back to conservative ratings.

A useful way to think about it: a static rating assumes the worst likely day, every day. A dynamic rating asks what today actually looks like.

Where the gains show up

The extra capacity tends to appear when conditions are favorable, such as cool, breezy days. That can line up well with wind generation, since windy conditions both increase wind output and cool the lines that carry it. On still, hot afternoons, a dynamic rating may show little or no extra room, which is why GETs are best understood as a way to use existing capacity more fully rather than a guaranteed increase at every hour.

Why Adoption Takes Time

If GETs can unlock capacity relatively cheaply, a fair question is why they are not everywhere already. Several practical reasons come up repeatedly:

  • Operating culture. Grid operators prize reliability above nearly everything. Changing long-standing practices requires confidence that new data is accurate and that systems will fail safely.
  • Software integration. Ratings that change hourly must be accepted by energy management systems, market platforms and planning tools that were built around fixed values.
  • Who benefits and who pays. Congestion relief may help generators, customers in another area, or the market broadly, while the cost falls on the utility that owns the line. Aligning those interests is a regulatory question.
  • Incentives. As the article notes, traditional utility business models reward capital spending. Some regulators have explored mechanisms that share savings from operational improvements with utilities to change that calculus.

What This Means for Someone Tracking a Project

For anyone following a data center or generation project that is waiting on transmission capacity, GETs suggest a few useful questions:

  • Is the constraint on a specific line or a few lines, or is it a broad regional shortage? Targeted constraints are where GETs help most.
  • Has the utility or grid operator studied dynamic ratings, power flow control or reconductoring as alternatives in its interconnection or transmission plans?
  • Would a faster, smaller upgrade allow a project to start operating in phases while larger work proceeds?
  • Are there pending regulatory proceedings that would require utilities to evaluate these options?

Questions readers ask

Are GETs new inventions? Many of the underlying ideas have existed for years. What has changed is the availability of low-cost sensors, better weather data, more computing power and growing pressure to add capacity quickly.

Do they make the grid less safe? When designed and operated properly, they are meant to keep lines within the same safety limits; they simply measure those limits more precisely instead of assuming the worst case.

Can a single technology solve congestion? Usually not. The strongest results tend to come from combining tools, such as dynamic ratings on one corridor, a power flow controller at a key substation, and reconductoring where wires are near the end of their life anyway.

Latest stories

View all

Power & Grid

A Maintenance Window Changes the Meaning of Redundancy

A facility’s normal arrangement is only one of its operating states. When equipment is removed from service for maintenance, the remaining paths may carry a different risk. A redundancy label needs to be read with that temporary configuration.

Published

on

Wires connected inside an electrical switch box

Photo: mostafa mahmoudi / Unsplash

A facility's normal arrangement is only one of its operating states. When equipment is removed from service for maintenance, the remaining paths may carry a different risk. A redundancy label needs to be read with that temporary configuration.

The operating distinction

Maintenance can remove a spare component, change a transfer path or increase the load on equipment that remains available. The operational question is which further interruption the system could tolerate in that state. That question may have a different answer from the one given for normal operation.

Advertisement

Temporary states deserve names that operators can recognize. If a system has several possible maintenance configurations, a generic instruction to use the backup can leave too much unstated. The arrangement being discussed should match the equipment actually removed from service.

A practical example

Imagine a hypothetical system with alternate power paths while both are available. During planned work on one path, the other becomes more important. A second task on a related component could create an exposure that neither maintenance activity would create alone.

Questions worth asking

The temporary configuration changes the relevant failure question. Describing the available paths during maintenance helps readers understand both why the work is necessary and which additional conditions the operating team must manage around it.

  • What protection remains while the selected equipment is unavailable?
  • Could another planned activity affect the same remaining support path?
  • What condition would postpone the work or require restoration of the normal arrangement?

What the evidence supports

This does not mean that maintenance should be avoided. Deferred work can increase other risks. It means that timing, dependencies and contingency arrangements belong in the planning discussion. Only qualified personnel following the site's procedures should operate or isolate electrical equipment.

The communication record should also identify when the temporary condition begins and how normal status is restored. Otherwise the next shift may inherit a narrower margin without realizing it. In a public explanation, this can remain high-level: the purpose is to distinguish resilience under normal conditions from resilience during planned work, not to publish sensitive switching instructions or suggest that every maintenance activity creates the same risk.

Advertisement

Describe resilience during the actual maintenance state, rather than borrowing the normal-state label without qualification.

Quick check

How much did you catch? Tap a question to see the answer.

1. Why read a redundancy label alongside maintenance plans?

Answer: Taking equipment out of service changes the risk on the paths that remain.

2. What question matters during maintenance?

Answer: Which further interruption the system could tolerate in that temporary state.

3. Why is “use the backup” too vague?

Answer: It doesn’t say which configuration matches the equipment actually removed from service.

Thinking in Operating States

A helpful habit is to describe a system as a set of named operating states rather than a single design. Each state has its own available paths and its own answer to the question of which further failure it could tolerate. In general terms, a facility might move through states such as these:

  • Normal. All designed paths and spare components are available.
  • Planned maintenance. A specific component or path is intentionally out of service for work.
  • Degraded after a fault. A component has failed unexpectedly and the system is running on the remaining paths.
  • Testing. The system is deliberately placed in a configuration to confirm that a function works.
  • Restoration. Work is complete and the system is returning to normal, but checks are not yet finished.

Describing which state applies, and what remains available in it, gives operators and readers a shared language. It also makes clear that the same facility can have different resilience at different times of the same week.

Planning a Maintenance Window Step by Step

The following outline describes how a planning discussion can be structured. It is not a switching procedure, which belongs to qualified personnel and site-specific methods.

  1. Name the affected equipment and resulting state. State clearly what will be out of service and what the remaining arrangement will be.
  2. Identify what remains protected. Describe which further faults the remaining paths could tolerate.
  3. Check for overlapping work. Review other planned activities, supplier visits and tests that could affect the same remaining path.
  4. Consider external conditions. Weather forecasts, utility notices and unusual load periods may favor a different timing.
  5. Set stop conditions. Agree in advance which developments would pause the work or trigger a return to the normal arrangement.
  6. Communicate the window. Inform affected teams and customers as appropriate, including start, expected end and restoration checks.
  7. Confirm restoration. Verify that normal status has returned and record it so the next shift knows.

Common mistakes

Two unrelated teams scheduling work on components that share a dependency is a classic problem, especially when change records are kept in separate systems. Another mistake is leaving a temporary state in place longer than planned without updating the shift record. A third is treating the restoration as complete as soon as equipment is energized, before checks confirm that the redundant path is genuinely available again.

What This Means for Customers and Readers

For a business hosted in a facility, maintenance notices are an opportunity to understand how resilience changes during planned work. A provider that explains the temporary state, the remaining protection and the stop conditions is communicating useful information. For readers following the industry, a redundancy label describes design intent; operating practice determines how well that intent holds up across the year.

Redundancy is a property of a particular moment, not a permanent label on the building.

Questions Readers Ask

Why not simply avoid maintenance to keep redundancy intact?

Deferred maintenance can increase the chance of unplanned failures. Planned work is usually the safer path when it is scheduled and coordinated carefully.

Can a facility remain fully redundant during maintenance?

Some designs are built to keep a spare path available while one path is under maintenance. Whether that applies depends on the specific design and the work involved.

Should customers be told about maintenance windows?

Many agreements include notification arrangements. The details vary by provider and contract.

What is a stop condition?

A pre-agreed event or reading that pauses the work or triggers restoration of the normal arrangement.

BOSSTOX is coming to iPhone

AI infrastructure explainers and news on iPhone, iPad and Apple Watch.

See BOSSTOX

Continue Reading

Power & Grid

Draw the Outage Boundary Before Comparing Backup Power

A backup-power claim becomes easier to understand when its boundary is drawn on a simple diagram. Keeping a server powered is different from keeping an entire service available, and neither statement describes every possible interruption.

Published

on

Rows of server racks in a data center

Photo: imgix / Unsplash

A backup-power claim becomes easier to understand when its boundary is drawn on a simple diagram. Keeping a server powered is different from keeping an entire service available, and neither statement describes every possible interruption.

The operating distinction

Electricity reaches the application through equipment with different jobs. A battery may support the server while a generator starts, yet the cooling controls, network equipment or building pumps could depend on another circuit. If any necessary part loses power, the application can stop even when its own power supply remains healthy.

Advertisement

The boundary also determines what an availability statement leaves out. A supplier may describe its equipment accurately while a customer reasonably hears a promise about the application. Those interpretations should be reconciled before a purchase or acceptance discussion.

A practical example

Consider a hypothetical hall with battery-backed racks and a cooling pump outside that protected boundary. A short interruption could leave the processors running while coolant circulation stops. The useful question is how the whole service behaves during that interval, rather than whether the rack has a battery.

Questions worth asking

An availability promise becomes clearer when the protected equipment and the promised user outcome are named together. Otherwise different parties can agree on the words while assuming different boundaries around the service.

  • Which supporting systems sit outside the protected power boundary?
  • What happens while the system transfers between power sources?
  • Which test demonstrates the claimed application-level behavior?

What the evidence supports

A drawing is not proof of performance. Actual protection depends on the installed arrangement, controls, maintenance state and tests. Two facilities using the same redundancy label can have different dependencies and different opportunities for a shared failure.

One useful reading exercise is to trace an ordinary user request through the drawing and mark every system it needs. Then consider an interruption at each boundary. This is a discussion exercise, not permission to disconnect equipment. It helps reveal which claims depend on assumptions that have not yet been stated and which supporting systems need evidence of their own before the broader service claim can be understood.

Advertisement

Define the service first, then examine the electrical and mechanical chain that keeps that service running.

Quick check

How much did you catch? Tap a question to see the answer.

1. Is keeping a server powered the same as keeping a service available?

Answer: No. Cooling, networking and building systems can sit on other circuits.

2. What helps make a backup-power claim clear?

Answer: Drawing its boundary on a simple diagram.

3. What can happen if a cooling pump sits outside the protected boundary?

Answer: Processors keep running while coolant circulation stops.

Going Deeper: Drawing the Diagram Step by Step

The exercise described above works best with a plain sheet of paper and a simple method. Here is one way to build the drawing for a hypothetical service before any comparison of backup power begins.

  1. Name the service outcome. Write one sentence at the top describing what users must be able to do, for example “customers can submit and receive answers within the agreed response time.” Everything else on the page exists to support that sentence.
  2. List the systems the request touches. Servers, storage, network switches, firewalls, the cooling loop serving those racks, the controls that run the cooling, and any building systems such as pumps or ventilation that the room depends on.
  3. Mark each system’s power source. Note which ones sit on battery-backed circuits, which rely on generator support only, and which run on ordinary utility power.
  4. Draw the boundary. Circle everything protected by the backup arrangement under discussion. Anything outside the circle is a dependency the claim does not cover.
  5. Walk through the transfer. For each system, ask what happens in the seconds between a utility interruption and the backup source taking over, and again when power returns.
  6. Note the evidence. Beside each system, write what test, document or record shows how it behaves. Blank spaces become the questions to ask.

Why the transfer interval deserves its own line

Batteries and generators do different jobs on different timescales. The battery carries the load immediately; the generator needs time to start and stabilize. Equipment that rides through the first interval may still be affected if it loses support during the second, or if controls reset when the source changes. Writing the sequence down makes those moments visible instead of assumed.

Common Gaps the Diagram Tends to Reveal

  • Cooling controls on a separate circuit. Chillers or pumps may be backed up, but the controllers that tell them what to do might not be.
  • Network equipment outside the protected room. A switch or router in another closet can become the single point that takes the service offline.
  • Shared upstream components. Two “redundant” paths that pass through one panel, one transfer switch or one fuel supply can fail together.
  • Monitoring that depends on the thing it monitors. If alarms run through systems that lose power, operators may not learn of a problem until users do.
  • Restart behavior. Some equipment does not return to normal operation automatically when power is restored and may need manual steps.

Questions to Bring to a Supplier or Facility Conversation

  • Which of the systems on our drawing does your claim cover, and which does it exclude?
  • Is the stated availability measured at the equipment, the room or the service?
  • What recent tests exercised the full transfer sequence, and what did they show?
  • How are maintenance periods handled, when part of the protection may be out of service?
  • Who is responsible for dependencies that sit between your scope and ours?

Questions Readers Ask

Is a redundancy label enough to compare two facilities? As noted above, the same label can describe different arrangements. The drawing and the evidence behind it are what make a comparison meaningful.

Who should draw the diagram? Ideally the people responsible for the service and the people responsible for the facility, together, so that assumptions on both sides end up on the same page.

Does this apply to small server rooms too? Yes. A single rack with a battery unit in an office can still depend on an unprotected air conditioner or network closet, so the same drawing exercise is useful at any scale.

How often should it be updated? Whenever equipment, layout or the service itself changes. A drawing that no longer matches the installed arrangement can be more misleading than none at all.

BOSSTOX is coming to iPhone

AI infrastructure explainers and news on iPhone, iPad and Apple Watch.

See BOSSTOX

Continue Reading

Power & Grid

FERC’s Large-Load Orders: The November 16 Grid Deadline Behind the AI Build-Out

FERC told all six grid operators it regulates to justify or rewrite their rules for connecting data centers and other large loads. After extensions, the answers are due November 16. Here is what to watch.

Published

on

Illustration of high-voltage transmission towers at dusk carrying power lines toward a lit data-center campus.

For most of the AI build-out, the hard question about a new data center has been about hardware: can the operator get the accelerators, the transformers and the cooling equipment? A slower question sits underneath all of them. Who decides how a 300-megawatt customer connects to the transmission grid, how long the study takes, and who pays if the project never arrives?

On June 18, 2026, the Federal Energy Regulatory Commission put that question to every grid operator it regulates. It issued six show cause orders, one each to PJM, MISO, SPP, CAISO, ISO New England and NYISO. Each order tells the operator and its transmission owners to either prove their current rules for large loads are just and reasonable or file new ones. After extensions, the responses are now due on November 16, 2026, for five of the six regions and November 20 for SPP.

This article explains what FERC asked for, where each step stands, and what the filings will tell readers following AI infrastructure.

Advertisement

How the grid got here

Generators that connect to the transmission grid have long had a federal process: a queue, studies and a standard agreement. Large consumers of electricity mostly did not. A new factory or data center usually connected through its local utility under rules set largely by states. That arrangement worked when a large industrial customer meant tens of megawatts. It strains when single campuses ask for hundreds of megawatts, sometimes with their own generation on site.

In October 2025 the Secretary of Energy used his authority under the Department of Energy Organization Act to send FERC an advance notice of proposed rulemaking on large-load interconnection, opened as Docket No. RM26-4-000. FERC says its staff reviewed more than 3,500 pages of public comments. Rather than issue a single national rule, the Commission chose tailored orders under Section 206 of the Federal Power Act, region by region. The rulemaking docket remains open.

FERC staff’s explainer describes the orders as covering facilities with maximum demand of at least 20 megawatts. They build on two earlier actions: a December 2025 order directing PJM to adopt transparent tariff rules for load co-located with generation, and FERC’s approval of SPP’s High Impact Large Load process.

The five issues every region must answer

Each order is tailored to its region, but all six identify the same five areas for reform:

  1. Faster, clearer study processes. A defined application path for large loads with accelerated study timelines, including evaluation of grid-enhancing and alternative transmission technologies.
  2. No cost shifting. Rules that keep upgrade costs for new large loads from landing on other customers, and public transparency into what those upgrades cost.
  3. Co-location and behind-the-meter generation. Clear tariff rules for data centers built next to, or behind the meter of, a power plant.
  4. Services for flexible loads. New transmission products, such as non-firm or contract-demand service, for customers willing to curtail during grid stress.
  5. Studying generation and load together. A process to study new generation alongside the nearby or co-located load it is built to serve.

The second item may matter most for public acceptance. FERC preliminarily found that operators do not publicly post enough data on the upgrades and costs needed to serve new large loads. The remedies it floated include posting each upgrade’s scope, cost and cost assignment, plus a central cost-transparency page on each operator’s website. FERC also asked whether operators should adopt standard cost recovery agreements among the grid operator, the transmission owner and the large customer. Those agreements would protect other ratepayers if a project is canceled or leaves early.

Advertisement

Two limits are easy to miss. The findings are preliminary, and FERC staff note the orders do not impose new transmission rates. The orders also apply going forward. FERC said they are not meant to disturb existing agreements or negotiations already near completion.

Where the clock stands

The orders set two deadlines. Within 30 days, each region had to file an informational report on how it will keep enough generation for existing and new large loads. MISO, for example, filed its report on July 20. Within 60 days, each region had to file its tariff response, unless it asked FERC to pause the case.

The operators asked for that pause, and FERC staff now list November 16 as the response date for five regions and November 20 for SPP. CAISO’s August 3 motion requested a 90-day abeyance so it could build a tailored filing with its transmission owners through an accelerated stakeholder process. MISO and its transmission owners filed a similar request the same day, and MISO reports that FERC granted it on August 14. In MISO’s case, responses are now due November 16 and answers to those responses December 16.

The pause has limits. CAISO’s motion notes that FERC said it would not grant abeyances reflexively. FERC capped them at 90 days and said it would look with great disfavor on requests to extend them further. That makes November 16 a firmer date than regulatory deadlines often are.

Some regional work is moving on a parallel track. CAISO’s published schedule takes its large-load proposal to its Board of Governors on October 28, ahead of the FERC filing. MISO separately filed interconnection reliability requirements for large loads on August 28, asking for a December 4 effective date.

What the filings will reveal

The responses will be long and technical. A handful of questions will say most of what matters about how quickly new AI capacity can connect, and on what terms.

  • Study timelines. Does each region commit to a defined number of days for a large-load study, and what readiness deposits or milestones must a project show to keep its place?
  • Interim service. Can a data center take non-firm or as-available service while network upgrades are built, and how often could that service be curtailed?
  • Financial security. How much must a large customer commit up front, and what happens to that money if the project shrinks or is canceled?
  • Co-location rules. How will regions treat a campus that sits beside a power plant, and what share of grid costs does it carry?
  • Cost posting. Will upgrade costs be published per project, so state regulators and the public can see who pays?

The answers will likely differ by region. A region that offers a fast, well-defined path with clear collateral rules may attract projects that can meet those terms. A region whose answers stay open-ended may keep seeing projects wait in queues and bilateral negotiations. Readers should treat any claimed speed-up with care until the tariff language is approved and the first projects move through it.

The orders also leave a gap. Utilities outside the six RTO and ISO regions, including much of the Southeast and West, are not directly covered. FERC Chairman Laura Swett encouraged those transmission providers to pursue similar reforms through their own filings. ERCOT, which runs most of the Texas grid, is not subject to the orders.

Why this belongs on an AI-infrastructure watch list

BOSSTOX has covered the physical limits on AI capacity: transformer lead times, transmission and local grid upgrades, behind-the-meter generation and on-site storage. The FERC proceeding is the rulebook that ties those pieces together. It decides how a project enters the grid, which upgrades it triggers, and who carries the risk if forecast demand does not arrive.

The dates to watch are concrete: CAISO’s board meeting on October 28, the six responses due November 16 and 20, answers due in mid-December, and the FERC orders that follow. BOSSTOX will review the filings once they are posted and report what each region actually committed to.

This article is general information about a regulatory proceeding. It is not investment, legal or regulatory advice. Filing dates come from FERC and grid-operator documents and may change; check the dockets for the latest.

Sources

  1. FERC, “FERC Launches Aggressive Targeted Action to Speed Large Load Integration,” June 18, 2026: ferc.gov
  2. FERC Office of Public Participation, “Cost Transparency and Customer Protection Initiatives in FERC’s June 2026 Show Cause Orders for Large Load Interconnections”: ferc.gov
  3. California ISO, “Motion for Abeyance,” Docket No. EL26-71-000, August 3, 2026: caiso.com
  4. MISO, “Large Load Working Group FERC Status Report,” September 9, 2026: misoenergy.org
  5. Akin Gump, “FERC Issues Landmark Show Cause Orders on Large Load Interconnection,” June 2026: akingump.com

BOSSTOX Research articles are drafted with AI assistance and reviewed by our editors before publication. See our editorial standards.

Continue Reading

Trending